Place of use
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.
Product Code | Dimension and Weights | Electrical Properties | |||||||||
Nominal Cross Section | Overall Diemeter ( ~ ) |
Net Weight ( ~ ) |
Standart Lenght | Max. Dc Conductor Resistance at 20◦ C | Current Carrying Capacity | ||||||
In Ground at 20° C | On Air at 30° C | ||||||||||
28-29000001 | 2x1.5 | 12.5 | 290 | 1000 | 12.1 | 32 | 20 | ||||
28-29000002 | 2x2.5 | 13.5 | 340 | 1000 | 7.41 | 42 | 27 | ||||
28-29000003 | 2x4 | 15.5 | 440 | 1000 | 4.61 | 54 | 37 | ||||
28-29000004 | 2x6 | 16.0 | 500 | 1000 | 3.08 | 68 | 48 | ||||
28-29000005 | 2x10 | 18.5 | 700 | 1000 | 1.83 | 90 | 66 | ||||
28-29000006 | 2x16 | 20.5 | 900 | 1000 | 1.15 | 116 | 89 | ||||
28-29000007 | 2x25 | 23.0 | 1200 | 1000 | 0.727 | 150 | 118 | ||||
28-29000008 | 2x35 | 25.5 | 1500 | 1000 | 0.524 | 181 | 145 | ||||
28-29000009 | 2x50 | 29.0 | 1950 | 1000 | 0.387 | 215 | 176 | ||||
28-29000010 | 2x70 | 32.0 | 2550 | 1000 | 0.268 | 264 | 224 | ||||
28-29000011 | 2x95 | 37.0 | 3400 | 1000 | 0.193 | 317 | 271 | ||||
28-29000012 | 2x120 | 41.5 | 4400 | 500 | 0.153 | 360 | 314 | ||||
28-29000013 | 2x150 | 45.0 | 5300 | 500 | 0.124 | 406 | 361 | ||||
28-29000014 | 2x185 | 50.0 | 6450 | 500 | 0.0991 | 458 | 412 | ||||
28-29000015 | 2x240 | 56.0 | 8150 | 500 | 0.0754 | 537 | 484 |